Tripp Lite SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS, Parallel for Capacity and Redundancy, Single & Dual AC Input - abea47ba2414

  • ✔ Trusted UK Supplier
  • ✔ Fast UK Delivery Available
  • ✔ Manufacturer Warranty Included
  • ✔ Expert Advice Available
  • ✔ Protects equipment from power loss
  • ✔ Prevents downtime and data loss
  • ✔ Suitable for business and home setups

    Tailor to your needs. Speak to a Specialist.
    Call: 0800 978 8988

    Please email me when stock is available

    Out of stock

    Need a quote?
    Battery Backup and VFI Operation Protect Critical Loads
    The SmartOnline® S3M60KXD IGBT UPS supports the continuous availability of your most important loads through all power conditions, providing a compact backup power platform that’s easy to manage and inexpensive to operate. Sophisticated voltage and frequency independentoperation and advanced IGBT rectifier technology with DSP control deliver reliable output power quality. Providing up to 60kVA of clean, continuous power, this 3-phase UPS system is perfect for critical applications in IT, communications, corporate, commercial, retail, financial, security, transportation, emergency and edge infrastructure environments.
    Best-in-Class Footprint for Easy Integration into Your Network Application
    This on-line double-conversion UPS system has a very small footprint of just 0.28 square meters. It requires less valuable space in your facility, and you can install the UPS system in spaces that would previously have required expensive retrofitting.
    Efficient Operation and Design Reduces Cost of Ownership
    This UPS benefits from highly efficient transformer-free double-conversion technology that delivers operating cost savings. It achieves 94% efficiency in double-conversion mode and up to 98% in ECO mode, reducing your power and cooling costs. A low THDiimproves generator compatibility. A low THDvand active power factor correction improve output performance. The hardware and firmware platform design reduces the number of unique boards, improving mean time to repairand resulting in reduced downtime. Built-in static and maintenance bypass transfer UPS load to utility power during faults, overloads and maintenance, which also avoids costly system downtime.
    External Batteries Supply Reliable Backup with Expandable Runtime Options
    The S3M60KXD uses external scalable battery cabinets, such as BP480V40, BP480V65 and BP480V100 , to provide up to three hours of backup support in case of a power failure. The UPS system automatically restarts after a lengthy power outage.
    Intuitive LCD Interface Delivers Important Performance Information at a Glance
    The interactive front-panel LCD interface displays critical operating conditions and diagnostic data, including operating mode, input/output voltage, load, battery voltage, backup runtime and fault conditions. Four LEDs provide information about line, bypass, battery and fault status.
    Network Management Card Offers Remote Monitoring and Control
    The optional WEBCARDLXwith the latest version of PowerAlert Device Manager firmwareprovides enhanced remote management capabilities, including customizable dashboard graphs to fit user preferences. The PADM20 upgrade and Tripp Lite’s PowerAlert Element Managersoftware form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations.
    Parallel Capability Provides Additional Capacity
    Connect up to three S3M60KX units in parallel using separate/shared battery cabinets for increased capacity or redundancy.
    2-Year Warranty Provides Peace of d
    The S3M60KXD is backed by a 2-year warranty, ensuring reliability and performance.
    OVERVIEW
    UPC Code 037332239808
    UPS Type On-Line
    INPUT
    Rated input current (Maximum Load) 93.2A
    Nominal Input Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
    Nominal Input Voltage Description 3-Phase Wye, 4 wire plus ground (L1, L2, L3, N, G)
    UPS Input Connection Type Hardwire
    Input Circuit Breakers 125A (3 pole)
    Input Phase 3-Phase
    Power Factor (Input)   .99PF (100% load)
    THDi   <3% (100% load)
    OUTPUT
    Output Volt Amp Capacity (VA) 60000
    Output Capacity (kVA) 60
    Output Watt Capacity (Watts) 54000
    Output kW Capacity (kW) 54.00
    Output Capacity Details Supports up to 100% load continuously in double conversion mode; Supports 100-110% load for 10 minutes, 110 to 130% load for 1 minute and greater than 130% for 1 second before switching to bypass mode; Inverter mode is automatically restored as load levels are reduced to less than 70%; Configuration options support up to 3 S3M30KX systems wired in parallel for increased capacity or fault-tolerant, redundant operation
    Power Factor   0.9
    Crest Factor   3:1
    Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
    Frequency Compatibility Details Automatic frequency selection
    Output Voltage Regulation (Line Mode) +/- 1%
    Output Voltage Regulation (Economy Line Mode) +/-11V of nominal
    Output Voltage Regulation (Battery Mode) +/- 1%
    Output AC Waveform (AC Mode) Pure Sine wave
    Output AC Waveform (Battery Mode) Pure Sine wave
    Nominal Output Voltage(s) Supported 220/380V 3-PH Wye; 230/400V 3-PH Wye; 240/415V 3-PH Wye
    Output Receptacles Hardwire
    Individually Controllable Load Banks   No
    BATTERY
    Expandable Battery Runtime Supports extended runtime with optional external battery packs. Please consult the owners manual.
    Expandable Runtime Yes
    External Battery Pack Compatibility    BP480V100 ;  BP480V100 -NIB;  BP480V40 ;  BP480V40 -NIB;  BP480V65
    DC System Voltage (VDC) +/- 240
    Battery Recharge Rate (Included Batteries) 9 hours to 90% (Internal batteries)
    VOLTAGE REGULATION
    Voltage Regulation Description Online, double-conversion power conditioning maintains output within 1% of the selected nominal voltage in online mode
    USER INTERFACE, ALERTS & CONTROLS
    Front Panel LCD Display LCD DISPLAY: offers a variety of graphical, text and numeric information to indicate a wide range of UPS operation and fault / warning conditions, including current operating mode, alarm status, load level, battery charge, input / output voltage & frequency, estimated runtime and more (see user manual for a detailed listing)
    Switches ON / ENTER BUTTON: turns the UPS on and confirms a selection from the settings menu; OFF / ESC BUTTON: turns off the UPS and returns to the previous item in the settings menu; TEST / UP BUTTON: initiates UPS self-test operation and advances to the next item in the settings menu; MUTE / DOWN BUTTON: silences the audible alarm and advances to the previous item in the settings menu; Press TEST/UP & MUTE/DOWN buttons simultaneously for 1 second to enter or exit the settings menu (See user manual for detailed information)
    Audible Alarm Alarms warn users of a variety of operational conditions: BYPASS MODE (beeps every 2 seconds), BATTERY MODE (beeps every 4 seconds), FAULT MODE (beeps continuously), OVERLOAD (beeps twice per second), OTHER WARNINGS (beeps once per second), FAULT (beeps continuously); All alarms can be silenced, except OVERLOAD & OTHER WARNINGS conditions
    LED Indicators 4 LEDs report BYPASS / LINE / BATTERY / FAULT modes
    PHYSICAL
    Primary Form Factor Tower
    Cooling Method Fans
    Installation Form Factors Supported with Included Accessories Tower
    Primary UPS Depth (mm) 790
    Primary UPS Height (mm) 1,010
    Primary UPS Width (mm) 360
    Shipping Weight (kg) 129.73
    UPS Housing Material Steel
    UPS Power Module Dimensions (Height x Width x Depth, mm) 1010 x 360 x 790
    UPS Power Module Weight (kg) 107.95
    ENVIRONMENTAL
    Operating Temperature Range 0 to +40C (32-104F)
    Storage Temperature Range 0 to +35C (32 to 95F) with battery; -15 to 60C (5 to +140F) without battery
    Relative Humidity 5 to 95%, non-condensing
    Operating Elevation (ft.) < 3280ft (Capacity de-rates by 1% for every 328ft over 3280ft )
    Audible Noise <70dBA at 1meter
    Operating Elevation (m) < 1000m (Capacity de-rates by 1% for every 100m over 1000m)
    COMMUNICATIONS
    Network Management Cards  WEBCARDLX ;  MODBUSCARDSV ;  RELAYCARDSV
    Network Monitoring Port Description Card accessory slot supports network management interface or programmable I/O relay card options
    Communications Cable DB9/RS-232 cable included
    Communications Interface DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
    LINE / BATTERY TRANSFER
    Transfer Time   Zero transfer time Online to Battery, Inverter to Bypass 0ms (Synchronous), and Inverter to ECO mode < 10ms.
    Low Voltage Transfer to Battery Power (Setpoint) 120V(Ph-N), 208V (Ph-Ph) @ 50% load / 176V (Ph-N), 305V (Ph-Ph) @ 100% load.
    High Voltage Transfer to Battery Power (Setpoint) 276 (Ph-N), 478V (Ph-Ph) @ 50% or 100% load.
    FEATURES & SPECIFICATIONS
    Grounding Lug Yes
    Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
    High Availability UPS Features   Automatic inverter bypass; Manual bypass switch; Auto Probe Monitoring (requires WEBCARDLX); Zero transfer time; On-Line/Double-Conversion
    Green Energy-Saving Features High efficiency economy mode operation
    STANDARDS & COMPLIANCE
    UPS Certifications CE
    Certification Details IEC/EN 62040-1:2008+A1 (Safety); IEC/EN 62040-2:2006 (Category C3)
    WARRANTY
    Product Warranty Period (International) 2-year limited warranty
    3-Phase Warranty Statement Tripp Lite 3-Phase UPS Factory Warranty

    Nationwide Onsite Maintenance is as easy as saying Bronze, Silver, Gold, Platinum.

    1: Plug and Play (400VA-3kVA) – Extended Warranty Contracts and Maintenance contracts

    For plug & play UPS Critical Power offers you a full range of distributed service packs. These competitively priced turn-key solutions optimize your UPS performances and enhance the availability of your equipment while meeting your financial constraints and technical requirements.

    Warranty Plus Extends your standard warranty up to 6 years, next working day replacement* with labour or without. Green tick
    Intervention, Provides one preventative maintenance visit, planned visit inside our outside hours. Green tick
    Battery Plus, Provides replacement batteries to site, next working day replacement or same day Green tick

    2: Hardwired (4kVA Upwards including Three Phase UPS) – Maintenance Contracts

    No matter what, your UPS, Generator, Cooling, Switchgear or Electrical Hardware must be ready to perform at all times. While every power solution we supply is backed-up by a comprehensive warranty with the manufacturer, maintenance plans to ensure business continuity are highly recommended, particularly for UPS systems from 4kVA. In particular, the battery set is of prime importance, and must be in good working order. With other consumables, such as fans and DC capacitors requiring regular maintenance and inspection logs reviewed to predict potential future problems.

    Services Included

    Silver Level

    Gold Level

    Platinum Level

    Platinum Plus

     

    Technical Hotline 24/7 Yes Yes Yes Yes Green tick
    Preventative Maintenance Yes Yes Yes Yes Green tick
    Remote Monitoring 24/7 Yes Yes Yes Yes Green tick
    Firmware Upgrades Yes Yes Yes Yes Green tick
    Emergency Response Yes Yes Yes Yes Green tick
    Labour Yes Yes Yes Yes Green tick
    Parts Yes Yes Yes option Green tick
    Monthly Event/Status Report option option option option Green tick
    Onsite Crash Kit option option option onsite Green tick
    Response Time 12 working hours 8 working hours 4 clock hours 4 clock hours Green tick
    Guaranteed Fix time – – – 4 Clock hours Green tick

    3: 24×7 Remote Monitoring Contracts –

    Remote monitoring of UPS, Generators, Air Conditioning, Site Access and Environmental Systems is essential to allow swift offsite investigation of fault reports and real-time monitoring of the site status, allowing the correct response to be created and dispatched to site.

    Engineer Installation and configuration during normal hours Green tick
    24×7 flexible status and remote monitoring. Green tick
    Encrypted communication, allowing safe offsite monitoring Green tick
    Alarms and events emailed and SMS texted automatically Green tick
    Firewall Friendly Green tick
    Cloud based status overview and multiple sites status on one screen Green tick
    Allows First Fix Response to Site Green tick

    4. IR Thermal Imaging Surveys – Infrared electrical inspection. Infrared electrical testing finds hot, dangerous problems quickly. Infrared electrical inspections find hot spots caused by defects in connections and components. – Contact us for more information.

    Detect system overloads, loose defective components and damaged switchgear. Infrared electrical testing finds hot, dangerous problems quickly. Infrared electrical inspections find hot spots caused by defects in connections and components.

    Infrared thermography is used to find areas of excess heat (caused by increased resistance) so that problems can be corrected before a component fails, causing damage to the component, creating safety hazards and productivity loss. Because increased heating is a sign of failure, infrared is the best diagnostic tool available for finding these hot connections in the early stages of degeneration.

    5. Switchgear – Contact us for more information.

    Switchgear maintenance is essential for efficient save plant operation and prolonged life span in the field Switchgear should be maintained as follows.

    • Live Maintenance – Unintrusive and consists of taking metering values, carrying out visual inspections and a thermal imaging survey of the switchboard. This is recommended to be carried out yearly.
    • Breaker Maintenance – Switchboard would need to be Isolated and all ACB’s and MCCB’s are maintained including visual and mechanical checks, greasing and secondary injection testing of the trip units. This is recommended to be carried out every 2 years.
    • Full Isolated Maintenance – Switchboard would need to be fully isolated from upstream supplies (HV). Breakers are maintained as per the above but also full maintenance carried out of the Switchboard to clean all compartments and carry out tightness checking of busbars and terminations etc. This is recommended to be carried out every 4 years.