Critical Power Supplies - Facebook-double Critical Power Supplies - Twitter-double Critical Power Supplies - Linkedin-double Critical Power Supplies - Google-plus-double Freephone 24 Hour: 0800 978 8988 Int: +44 (0)1844 340122
x

Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire - SU6000RT3UHVXL

NOTE: Images are for illustrative purposes. If unsure please ask our sales team.

Part Number: SU6000RT3UHVXL

Product (inc VAT):
Discontinued

Discontinued

Tripp Lite Smart Online UPS systems offer high performance power protection ideal for critical server and network equipment in datacenters, computer rooms and network closets. Online, double-conversion Uninterruptible Power Supply (UPS) maintains perfectly regulated output power by continuously converting raw AC input to DC, then re-converting output back to AC. Fully regulated sine wave AC output with +/-2% voltage regulation powers network equipment continuously, even during severe brownouts and overvoltages, all without depleting UPS battery reserves. Maintains battery-derived AC output during power failures with zero transfer time. Extended runtime options aVAilable. Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a Variety of UPS setup and configuration options. Highly efficient operation in optional economy mode saves Btu heat output and energy costs. Network management interfaces support communicationtions via RS-232, contact-closure and optional SNMPWEBCARD network interface. Built-in DB9 port offers both enhanced RS-232 data and basic contact closure monitoring ability. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. LED display reports UPS operating mode, line power availability, battery mode operation, inverter operation, ECO mode status and output power availability. Audible alarm with push-button momentary alarm-cancel and silent-mode LCD configuration options. Programmable self-test. Fault-tolerant auto-bypass mode. Field-replaceable, hot-swappable internal batteries and external battery packs.
- True on-line, double conversion UPS provides pure, sine wave AC output at all times
- World-wide compatibility with Euro 50Hz and High Voltage North American 60Hz power
- Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
- Removes harmonic distortion, electrical impulses, frequency VAriations and other hard to solve power problems
- 6000VA/4200 watt power capacity with hardwire input/output connections
- Accepts input voltages between 156 and 276, regulating output within 2% of selectable 200/208/220/230/240v AC output
- 30 minutes runtime at half load (2100W) / 12 minutes at full load (4200W) with included BP240V10RT3U external battery pack
- Expandable runtime with multiple external battery packs
- InnoVAtive design makes unit adaptable for rack mount, tower, or stacking applications
- Power module and battery pack require only 3 rack spaces each (6U total rack space usage)
- DB9 serial port for network interface; SNMP compatible
- Slot for optional SNMP/web card (part# SNMPWEBCARD)
- PowerAlert unattended shutdown software and 6 ft. network cable included
- Fault tolerant electronic bypass maintains utility output during a Variety of UPS fault conditions
- Diagnostic LEDs
- Mounting hardware included with each 3U module for 4 post rack mount installation, 2 post telecom rack compatible with separate purchase 2POSTRMKITHD (2 required)
- Includes RJ11 EPO (emergency power off) port and interconnection cable
- $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only)

Power
Output power4200 W
Input operation voltage (min)200 V
Input operation voltage (max)240 V
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Surge energy rating480 J
Emergency Power Off (EPO)Yes
Power factor0.7
Crest factor3:1
Output power capacity6000 VA
Performance
UPS topologyDouble-conversion (Online)
LED indicatorsYes
Noise level60 dB
Audible alarm(s)Yes
Features
UPS topologyDouble-conversion (Online)
Output power4200 W
Input operation voltage (min)200 V
Input operation voltage (max)240 V
Output operation voltage (min)200 V
Output operation voltage (max)240 V
Surge energy rating480 J
Emergency Power Off (EPO)Yes
Power factor0.7
Noise level60 dB
Crest factor3:1
Audible alarm(s)Yes
Output power capacity6000 VA
Input frequency50/60 Hz
Ports & interfaces
AC outlet typesTerminal
Power plugTerminal
RS-232 ports1
Battery
Typical backup time at half load30 min
Typical backup time at full load12 min
Hot-swap batteryYes
Cold startYes
Automatic battery testYes
Design
Rack capacity6U
Form factorRackmount/Tower
LED indicatorsYes
Product colourBlack
DisplayLCD
Cooling typeActive
CertificationUL1778
CSA
NOM
CE
GOST
SASO
IRAM
FCC
RoHS complianceYes
Housing materialSteel
Operational conditions
Operating temperature (T-T)0 - 40 °C
Storage temperature (T-T)-15 - 50 °C
Cooling
Cooling typeActive
Packaging data
Package width1016 mm
Package depth1219 mm
Package height699 mm
Package weight146.6 kg
Certificates
CertificationUL1778
CSA
NOM
CE
GOST
SASO
IRAM
FCC
RoHS complianceYes
Other features
Relative humidity0 - 95%
Output connection typeHardwire
Operating temperature (T-T)32 - 104 °F
Management platformSNMP/WEB
Weight & dimensions
Package width1016 mm
Package depth1219 mm
Package height699 mm
Package weight146.6 kg

Onsite Maintenance is as easy as 1, 2, 3, 4. Contact us for further information 24x7 on our sales number.


1: Plug and Play (400-3kVA) - Extended Warranty Contracts from 1 to 5 years from £5.99 per month ex VAT

For plug & play UPS Critical Power offers you a full range of distributed service packs. These competitively priced turn-key solutions optimize your UPS performances and enhance the availability of your equipment while meeting your financial constraints and technical requirements.

Warranty Plus Extends your warranty up to 3 years, next working day replacement
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 1
Warranty Plus Extends your warranty up to 5 years, next working day replacement
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 2
Intervention, Provides one preventative maintenance visit, planned visit  
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 3
Battery Plus, Provides replacement batteries to site, next working day replacement
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 4
Warranty One Extends your warranty up to 1 year, next working day replacement  
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 5


2: Hardwired (4kVA Upwards– Onsite Maintenance Contracts from 1 to 5 years from £49.99 per month ex VAT

No matter what, your UPS, Generator, Cooling, Switchgear or Electrical Hardware must be ready to perform at all times. While every power solution we supply is backed-up by a comprehensive warranty with the manufacturer, maintenance plans to ensure business continuity are highly recommended, particularly for UPS systems from 1kVA. In particular, the battery set is of prime importance, and must be in good working order. With other consumables, such as fans and DC capacitors requiring regular maintenance and inspection logs reviewed to predict potential future problems.

Services Included

Silver Level

Gold Level

Platinum Level

 

Technical Hotline 24/7
Yes
Yes
Yes
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 6
Preventative Maintenance
Yes
Yes
Yes
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 7
Remote Monitoring 24/7
Yes
Yes
Yes
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 8
Firmware Upgrades
Yes
Yes
Yes
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 9
Emergency Response
Yes
Yes
Yes
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 10
Labour
Yes
Yes
Yes
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 11
Parts
Yes
Yes
Yes
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 12
Monthly Event/Status Report
option
option
option
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 13
Onsite Crash Kit
option
option
option
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 14
Response Time
12 working hours
8 working hours
4 clock hours
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 15


3: 24x7 Remote Monitoring Contracts from 1 month to 5 years from £29.99 per month ex VAT

Remote monitoring of UPS, Generators, Air Conditioning, Site Access and Environmental Systems is essential to allow swift offsite investigation of fault reports and real-time monitoring of the site status, allowing the correct response to be created and dispatched to site.

Engineer Installation and configuration during normal hours
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 16
24x7 flexible status and remote monitoring.      
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 17
Encrypted communication, allowing safe offsite monitoring    
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 18
Alarms and events emailed and SMS texted automatically    
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 19
Firewall Friendly
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 20
Cloud based status overview and multiple sites status on one screen
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 21
Allows First Fix Response to Site
Critical Power Supplies - Tripp lite smartonline 208/240, 230v 6kva 4.2kw double-conversion ups, 6u rack/tower, extended run, oversize batteries, network card slot, db9, hardwire image 22

4. IR Thermal Imaging Surveys - Infrared electrical inspection. Infrared electrical testing finds hot, dangerous problems quickly. Infrared electrical inspections find hot spots caused by defects in connections and components.

Detect system overloads, loose defective components and damaged switchgear. Infrared electrical testing finds hot, dangerous problems quickly. Infrared electrical inspections find hot spots caused by defects in connections and components.

Infrared thermography is used to find areas of excess heat (caused by increased resistance) so that problems can be corrected before a component fails, causing damage to the component, creating safety hazards and productivity loss. Because increased heating is a sign of failure, infrared is the best diagnostic tool available for finding these hot connections in the early stages of degeneration.

.

Let us know what you think of this product

If you have purchased this from us in the past then please take some time to review the product, along with the quality of service you received from us!