Webinar Recording – Join Jason Koffler and Ian Bitterlin for a live discussion on Ensuring Business Continuity
Equip yourself with actionable knowledge to safeguard the continuity of your business.
Delve into the expertise of our distinguished speakers, Ian Bitterlin and Jason Koffler, esteemed veterans in power systems. Gain invaluable insights and practical strategies to fortify your business against disruptions.
Explore the pivotal role of power quality and discover effective backup power solutions to bolster resilience and maintain seamless operations.
Question 1
Do the two separate supplies to a dual corded server have to be in synch?
Answer
No, they can be of different voltage and frequency (including DC with careful choice of voltage) and asynchronous. The reason is that the SMPSs are based on transistorised switches that convert whatever energy is supplied to DC (typically 300VDC from a 230VRMS AC supply) and then chop it down to a highly regulated dual output 12.1VDC and 5.1VDC supplies to the server motherboard and sub-boards. The two SMPSs are connected in parallel DC, hence independent of AC voltage and frequency.
Question 2
How about Failure Mode Analysis at design, rather than tiering?
Answer
The Availability Class (or Tier) is akin to a train timetable – it sets out goals for maintenance (non-concurrent or concurrent) and fault-tolerance (or not) to the worst external event, but does not predict mission-success that a FMA process might suggest. FMA cannot help with human intervention and error etc.
It is interesting to note that the original Uptime Institute white-paper(s) did suggest minimum Availability in terms of percentage availability, e.g., 99.99% for Tier IV, that was claimed to include (amongst 16 failure categories) power, cooling, fibre, EPO, and fire suppression.
Perversely, the Availability for the four Tiers was quickly converted to “X minutes of downtime per year”, e.g., resulting in a 99.99% Tier IV facility being off-line for 5.3 minutes every year. Even a ‘single event’ 5.3-minute failure reflects a disastrous data centre performance but, far worse, the 5.3 minutes could have been met but more than one short failure every day! As a result of repeated questioning, these percentages, that were never supported by a calculation method, were soon withdrawn.
Question 3
Single corded devices can be connected to an in-rack ATS. Yes, but an STS, not an ATS.
Answer
An ATS is an electromechanical switch which takes (much) longer to operate in an emergency transfer – e.g., 30-50ms compared to the “worst in class” 6ms of some ICT hardware. Search for The Green Grid website and white-paper on voltage susceptibility.
An STS is an transistor based electronic switch which takes no more than 4ms to operate in an emergency transfer.
It is worth noting that STSs (and ATSs on other M&E plant) have to be managed as they do not share the load across A & B sources but have to be biased to either A or B. Good management, by biasing hardware 50/50 across A & B source, ensures that the transfer load is limited.
Question 4
Is rotary UPS dead?
Answer
No, certainly not yet, although hybrid-rotary is closer to its sunset than diesel-rotary. It has a significant efficiency penalty compared to modern static UPS, especially at partial load that is endemic in most colocation and enterprise. When compared to modular static UPC at 35% load (a typical maximum in a 70% loaded dual-bus ICT) the energy costs are unsustainable in this world of energy being of paramount importance.
All types of rotary UPS have a higher voltage distortion than static UPS when feeding an ICT non-linear load, although hybrid-rotary still has a significant advantage over static UPS in single-module reliability, but that comes with increased CapEx and OpEx.
Question 5
What are your thoughts about UPS systems offering grid services?
Answer
An unsound operational principle, technically without significant cost or complexity but best summarised by one data centre operator in the statement “…my UPS is there to protect my load from the grid, not support it in moments of distress”.
There are several facets to the argument, that include:
Battery autonomy should, and increasingly is, be no more than 1-2 minutes – for example with ultra-thin pure-lead VRLA which is >12 year Design Life and <9 year Service Life – and not 5-10 minutes. As an aside, small, light, and very easy to detect and suppress any fire risk. There should not be superfluous energy in the battery that could be utilised.
If the grid is under pressure (e.g. needing frequency support) and the battery momentarily discharges back through the rectifier, what happens if the grid collapses? The rectifier fuses could rupture and the UPS trips to bypass, to the utility that is failing. The ICT load is disconnected and the UPS cannot be restarted for several hours during service and spares logistics.
In the UK there is probably less than 1% of the grid load that could be supported by suitable UPS (rated capacity, technically capable, and operator willingness). The reward is insignificant compared to the risk of failure, real or perceived.
For nearly two decades in the UK we have had Dinorwig pumped-storage power station in North Wales to provide short term grid support (STOR and/or frequency correction) with 9GWh of water storage, about 25% of our winter grid demand for one-hour. The six turbines generate a peak 1.8GW. We don’t need a 1% contribution from UPS.
As the UK moves forward with more wind capacity we have no choice but to install grid-scale battery storage, although this will eventually be phased out by multiple (>20) SMRs. Grid-scale storage is far preferable to small distributed near the edge of the grid.
Question 6
Biggest UPS development driver in past 10-15 years was efficiency…now all dual conversion units
(in online mode) are v high efficiency..was is biggest driver for UPS development in next 10 years?
Regarding the reliability of new UPS’s, Does having a modular UPS filled with multiple power/battery
modules have a higher failure rate due to more components than a single static UPS? Also thoughts o
n modular UPS’s?
Answer
Twenty years ago we introduced transformer-free UPS which had the consequential advantage of the transistor based rectifier and there was a leap forward in efficiency as well as 50% space and weight saving. With double-conversion transformer-less, IGBT rectification, and inversion, the way was clear to reach a ubiquitous 96.7% efficiency at full-load by 2010, and with an added bonus of 97% efficiency at 50% load.
Not resting on laurels, then came along line-interactive topology reaching a little over 98%, not a new idea (dating from Silcon in Denmark during the mid-90s ) although the bulk of the industry (and client preference to a point) stayed with double conversion.
The really big-idea came with ‘eco-mode’. When the grid was behaving itself, the UPS automatically switched itself into bypass and the efficiency hit 99%. But ‘eco-mode’, although capable of switching to/from the utility (usually with no break but always in <4ms), was cheap to implement, came ‘free’ with most double-conversion UPS, and worked reliably, it was not embraced by all users despite the huge efficiency and cost gains.
Finally, the UPS OEMs addressed the partial load problem and ‘modular’ UPS, where UPS was built from multiple smaller modules that were turned ‘off’ if not needed, was innovated and efficiency of 96% was available in double conversion mode all the way down to <20% connected load.
One UPS OEM successfully combined all three operating modes, double conversion, line-interactive, and eco-mode, in one UPS system with automatic selection via utility/generator monitoring. The result was high energy savings, although the user still has the option of not enabling eco-mode.
But all of this history is about to change to a situation where the UPS will reach 99.3% in the highest perceived reliability double-conversion mode. This will spell the end of eco-mode, and line-interactive, although modular will probably remain for partial load. It has already started to change, in Japan from 2018, and IT is being sold in the USA, but not yet in Europe.
The technology is ‘simply’ to change from silicon based IGBTs to silicon-carbide (SiC) IGBTs. Best known as the abrasive carborundum, SiC currently carries a 20% price premium but the real barrier to adoption is the UPS OEMs who would need to revamp all their designs, inventory, documentation, and service training – a huge investment. In the USA, where energy is still low cost compared to other regions, the barrier is more to do with reward-to-cost behaviour.
The technology is fully field proven (since 2018) and there is no ‘greenwashing’ involved.
Question 7
There is NO doubt that the higher the component count, the lower the reliability. In the case of modular UPS the larger the building block, the better. No more than 10 modules (3ph) should be used in a single modular UPS system, OR the system should be programmed to run at N+2 rather than N+1.
Answer
It can be lower cost to “build your own” modular system and use manual control of duty/standby operation based on regular load monitoring.
Generally avoid modular products that do not switch modules ‘off’ at lower load, because they are built to save energy not be more reliable, and always advise users to enable the modularity control.
Question 8
Static UPS on IP BUS? One manufacturer claiming they make this
Answer
IP-Bus (Isolated-Parallel Bus) was innovated (and patented in the USA, but OEMs seem to ignore that?) to build larger systems at LV that would be available using the largest LV switch of 6300A (a system module of about 3.7MW).
The load has to be sectionalised into N parts and the N rotary UPS installed between the sections with a total capacity of N+1. Each section is isolated from the adjacent sections by large inductances (chokes) which limit inrush and rebalancing current when one UPS fails of is withdrawn for service.
The idea suits rotary UPS very well as, with its inherent inductance, it is relatively slow to react.
Static-UPS is inherently fast to react, and additional measures would have to be taken to damp-down the response. Only fuses would be fast enough to ensure isolation and the overall reliability would be compromised.
However, it is important to note that static-UPS doe not NEED IP-Bus as it has modular capacity that means that N+1 can be achieved by adding one small module. On the DRUPS solution the +1 can only be reach by adding one very large module, at proportionally high cost.