Battery Backup and VFI Operation Protect Critical LoadsThe SmartOnline® S3M120KX IGBT UPS supports the continuous availability of your most important loads through all power conditions, providing a compact backup power platform that’s easy to manage and inexpensive to operate. Sophisticated voltage and frequency independentoperation and advanced IGBT rectifier technology with DSP control deliver reliable output power quality. Providing up to 120kVA of clean, continuous power, this 3-phase UPS system is perfect for critical applications in IT, communications, corporate, commercial, retail, financial, security, transportation, emergency and light industrial environments.Best-in-Class Footprint for Easy Integration into Your Network ApplicationThis on-line double-conversion UPS system has a very small footprint of just 0.54 square meters. It requires less valuable space in your data center, and you can install the UPS system in spaces that would previously have required expensive retrofitting.Efficient Operation and Design Reduces Cost of OwnershipThis IGBT UPS benefits from highly efficient transformer-free double-conversion technology that delivers operating cost savings. It achieves 94% efficiency in double-conversion mode and up to 98% in ECO mode, reducing your power and cooling costs. A low THDiimproves generator compatibility. A low THDvand active power factor correction improve output performance. The hardware and firmware platform design reduces the number of unique boards, improving mean time to repairand resulting in reduced downtime. Built-in static and maintenance bypass transfer UPS load to utility power during faults, overloads and maintenance, which also avoids costly system downtime.External Batteries Supply Reliable Backup with Expandable Runtime OptionsThe S3M120KX uses external scalable battery cabinets, such as BP480V40, BP480V65 and BP480V100 , to provide up to three hours of backup support in case of a power failure. Add the optional TEMPC100200 thermostat kit to enable temperature-compensated charging for optimized battery lifespan. The UPS system automatically restarts after a lengthy power outage.Intuitive Color Touchscreen Display Delivers Important Performance Information at a GlanceThe largefront-panel color interface enables comprehensive local monitoring and control capability. It displays critical operating conditions and diagnostic data, such as phase load levels, available runtime, alarm status, battery charge, and voltage and frequency values. Six LEDs indicate bypass, on-line, inverter, battery and alarm/fault modes.Network Management Card Offers Remote Monitoring and ControlThe optional WEBCARDLXwith the latest version of PowerAlert Device Manager firmwareprovides enhanced remote management capabilities, including customizable dashboard graphs to fit user preferences. The PADM20 upgrade and Tripp Lite’s PowerAlert Element Managersoftware form a powerful tool for expanding maintenance functions in large installations, including firmware update checks and backup and restoration of device configurations. Auto Probe allows a UPS with switched loads to automatically reboot devices if a network communication failure is detected. This preserves uptime and imizes the time and expense associated with on-site support.Parallel Capability Provides Additional CapacityConnect two S3M120KX units in parallel using separate/shared battery cabinets for increased capacity and fault tolerance .
Nationwide Onsite Maintenance is as easy as saying Bronze, Silver, Gold, Platinum.
1: Plug and Play (400VA-3kVA) – Extended Warranty Contracts and Maintenance contracts
For plug & play UPS Critical Power offers you a full range of distributed service packs. These competitively priced turn-key solutions optimize your UPS performances and enhance the availability of your equipment while meeting your financial constraints and technical requirements.
| Warranty Plus Extends your standard warranty up to 6 years, next working day replacement* with labour or without. |
 |
| Intervention, Provides one preventative maintenance visit, planned visit inside our outside hours. |
 |
| Battery Plus, Provides replacement batteries to site, next working day replacement or same day |
 |
2: Hardwired (4kVA Upwards including Three Phase UPS) – Maintenance Contracts
No matter what, your UPS, Generator, Cooling, Switchgear or Electrical Hardware must be ready to perform at all times. While every power solution we supply is backed-up by a comprehensive warranty with the manufacturer, maintenance plans to ensure business continuity are highly recommended, particularly for UPS systems from 4kVA. In particular, the battery set is of prime importance, and must be in good working order. With other consumables, such as fans and DC capacitors requiring regular maintenance and inspection logs reviewed to predict potential future problems.
3: 24×7 Remote Monitoring Contracts –
Remote monitoring of UPS, Generators, Air Conditioning, Site Access and Environmental Systems is essential to allow swift offsite investigation of fault reports and real-time monitoring of the site status, allowing the correct response to be created and dispatched to site.
| Engineer Installation and configuration during normal hours |
 |
| 24×7 flexible status and remote monitoring. |
 |
| Encrypted communication, allowing safe offsite monitoring |
 |
| Alarms and events emailed and SMS texted automatically |
 |
| Firewall Friendly |
 |
| Cloud based status overview and multiple sites status on one screen |
 |
| Allows First Fix Response to Site |
 |
4. IR Thermal Imaging Surveys – Infrared electrical inspection. Infrared electrical testing finds hot, dangerous problems quickly. Infrared electrical inspections find hot spots caused by defects in connections and components. – Contact us for more information.
Detect system overloads, loose defective components and damaged switchgear. Infrared electrical testing finds hot, dangerous problems quickly. Infrared electrical inspections find hot spots caused by defects in connections and components.
Infrared thermography is used to find areas of excess heat (caused by increased resistance) so that problems can be corrected before a component fails, causing damage to the component, creating safety hazards and productivity loss. Because increased heating is a sign of failure, infrared is the best diagnostic tool available for finding these hot connections in the early stages of degeneration.
5. Switchgear – Contact us for more information.
Switchgear maintenance is essential for efficient save plant operation and prolonged life span in the field Switchgear should be maintained as follows.
- Live Maintenance – Unintrusive and consists of taking metering values, carrying out visual inspections and a thermal imaging survey of the switchboard. This is recommended to be carried out yearly.
- Breaker Maintenance – Switchboard would need to be Isolated and all ACB’s and MCCB’s are maintained including visual and mechanical checks, greasing and secondary injection testing of the trip units. This is recommended to be carried out every 2 years.
- Full Isolated Maintenance – Switchboard would need to be fully isolated from upstream supplies (HV). Breakers are maintained as per the above but also full maintenance carried out of the Switchboard to clean all compartments and carry out tightness checking of busbars and terminations etc. This is recommended to be carried out every 4 years.